IEEE/ANSI Device Numbers Cheat Sheet (C37.2)
If you have ever looked at a substation or switchgear one-line and wondered why there are two-digit numbers scattered around the breakers and little relay circles — a 52 here, a 50/51 there, an 87T on the transformer — those are device function numbers from ANSI/IEEE C37.2. They are the shorthand North-American protection engineers use to say what a device does without writing it out in words.
The standard assigns each protective, control, and auxiliary function a number from 1 to 99. A "51" is always an AC time-overcurrent relay, anywhere in the world a C37.2 drawing is used. That consistency is the whole point: a relay tech in Texas and a consultant in Toronto read the same one-line the same way. This page is a working cheat sheet of the numbers you will actually meet on single-line diagrams, plus the suffix letters and combinations that modify them.
Draw a protected feeder — breaker, CT and relay — on smartsld.com — freeHow the numbering works
A device number is a function identifier, not a part number. It tells you the job the device performs; the manufacturer, model, and settings are called out separately. A few things are worth knowing before you read the table:
- 52 is the circuit breaker itself. It is the one number that is not a relay — it is the power switching device. You will see it more than any other symbol on a one-line.
- Protective relays cluster in the 20s through 80s. Overcurrent (50/51), voltage (27/59), directional (67), differential (87) and frequency (81) are the bread-and-butter feeder and transformer functions.
- The number stays the same whether the function lives in an electromechanical relay or a modern microprocessor relay. One digital relay may perform 50, 51, 67, 27, 59, 81, and 87 all at once — each is still cited by its C37.2 number.
On a diagram, the function is usually drawn as a circle (the relay) with its number inside, tapped from a current transformer (CT) or voltage/potential transformer (VT/PT) and wired to trip the breaker it protects.
Master device number reference
These are the functions you will encounter most often on distribution, generation, and industrial one-lines. The table is condensed from ANSI/IEEE C37.2; confirm exact wording against the current edition of the standard when it matters for a submittal.
| No. | Function | Typical use |
|---|---|---|
| 21 | Distance relay | Impedance-based fault detection. Primary and backup protection on transmission lines and generator step-up connections. |
| 25 | Synchronism-check / synchronizing | Confirms two systems match in voltage, frequency, and phase angle before a breaker closes — tie breakers and generator paralleling. |
| 27 | Undervoltage relay | Trips or alarms on sagging voltage. Motor protection, undervoltage load shedding, and part of anti-islanding schemes. |
| 32 | Directional power relay | Detects real-power flow in a defined direction. Reverse-power protection for generators and utility interties. |
| 37 | Undercurrent / underpower relay | Detects loss of load — pump loss of prime, conveyor break, or an unloaded motor. |
| 40 | Loss-of-field (field) relay | Detects loss of excitation on synchronous generators and motors. |
| 46 | Negative-sequence / phase-balance current | Detects current unbalance, open phase, or phase reversal. Motor and generator protection. |
| 47 | Phase-sequence / phase-balance voltage | Detects phase reversal or voltage unbalance — supply-quality and rotation checks. |
| 49 | Thermal relay | Overload protection modeling machine or transformer heating, often driven by RTDs or a thermal replica. |
| 50 | Instantaneous overcurrent relay | Trips with no intentional delay above a set current — fast clearing of high-magnitude faults. |
| 51 | AC time-overcurrent relay | Inverse time-current curve. The backbone of coordinated overcurrent protection and backup. |
| 52 | AC circuit breaker | The power breaker itself — not a relay. The most common number on any one-line. |
| 55 | Power-factor relay | Monitors or controls power factor. Capacitor-bank switching and synchronous-machine control. |
| 59 | Overvoltage relay | Trips or alarms on sustained overvoltage. Anti-islanding, capacitor, and generator protection. |
| 63 | Pressure switch | Sudden-pressure, Buchholz, or gas-accumulation protection on liquid-filled transformers. |
| 67 | AC directional overcurrent relay | Overcurrent that only operates for current in one direction. Loops, parallel feeders, and ties. |
| 79 | AC reclosing relay | Automatically recloses a breaker after a trip. Common on overhead distribution feeders. |
| 81 | Frequency relay | Over/under-frequency (81O/81U) and rate-of-change (81R). Load shedding and anti-islanding. |
| 85 | Pilot / carrier / communications relay | The communications-channel element in pilot and line-differential schemes (paired with 87L). |
| 86 | Lockout relay | Hand-reset auxiliary that trips and locks out multiple devices until manually reset after a major fault. |
| 87 | Differential relay | Compares current entering vs leaving a zone. Primary protection for transformers, buses, machines, and lines. |
| 94 | Tripping / trip-free relay | Fast auxiliary relay that trips the breaker and provides the trip-free (anti-pump) function. |
Suffix letters
A bare number tells you the function; a suffix letter tells you what it is protecting or which quantity it measures. These are the ones you will see constantly:
| Suffix | Meaning | Example |
|---|---|---|
| N | Neutral / residual | 51N — time overcurrent operating on the residual (the vector sum of the three phase CTs). |
| G | Ground | 51G — time overcurrent fed from a dedicated ground or core-balance (zero-sequence) CT. |
| T | Transformer | 87T — differential protection whose zone is a power transformer. |
| B | Bus | 87B — differential protection whose zone is a bus. |
The N vs G distinction trips people up. Both catch ground faults, but N derives ground current from the residual connection of the phase CTs, while G measures it directly with a separate ground CT. Conventions vary slightly between manufacturers, so check the relay's own documentation. Other suffixes you may meet include L (line, as in 87L), A (alarm), and 1/2 to number multiple identical devices.
Common combinations
Functions are routinely stacked when a single device performs several jobs. A few you should be able to read on sight:
- 50/51 — instantaneous plus time overcurrent in one phase-overcurrent element. The single most common relay callout on a feeder.
- 50N/51N — the same instantaneous-plus-time pair applied to the neutral/residual for ground-fault protection.
- 27/59 — combined under- and overvoltage, often a single voltage-protection block.
- 67N — directional ground overcurrent, used where fault current can flow either way through the point of measurement.
- 87T — transformer differential; 87B bus differential; 87L line-current differential (paired with a 85 communications channel).
How relays and breakers get labelled on an SLD
On the diagram the mapping is straightforward once you know the convention:
- The breaker carries the number 52, usually with an equipment tag alongside it (for example
52-M1for main breaker 1). The symbol is the breaker itself — a small square in the conductor (ANSI) or a switch with crossbars (IEC). - The relay is drawn as a circle containing its function number or numbers (
50/51,87T,27). A dashed line ties it to the CT or VT that feeds it, and another dashed line runs to the trip coil of the breaker it operates. Dashed = secondary and control wiring; solid = primary power. - Instrument transformers — the CT and VT/PT that the relays read — are shown in the primary circuit and labelled with their ratios (for example
600:5). - Auxiliaries like the 86 lockout and 94 trip relay usually sit near the breaker they command; the 86 often shows the several breakers it locks out.
Put together, a typical protected feeder reads: bus → CT → breaker 52, with a 50/51 (and often 50N/51N) relay sensing the CT and tripping the 52 through an 86 lockout. Read enough of them and the pattern becomes automatic.
Lay out a switchgear one-line with breakers and relays — free in the browserNorth-American vs IEC practice
Device numbers are a North-American convention. C37.2 numbering dominates in the United States, Canada, and markets that follow ANSI practice. Elsewhere — Europe, most of Asia, Australia, the Middle East — drawings follow IEC conventions and generally do not use these two-digit numbers.
Under IEC, protection functions are more often written out or referenced through IEC 61850 logical nodes (for example PTOC for a time-overcurrent function, PDIF for differential, PDIS for distance). Many relay vendors and multinational projects now print both — the familiar ANSI number and the 61850 logical node — so the two systems increasingly appear side by side rather than in competition. If you are reading a drawing and the protection is labelled by function name or a four-letter node instead of a number, you are almost certainly on an IEC-style document. When a project spans both worlds, agree the convention up front and keep one drawing internally consistent.
C37.2 is periodically revised and relay manufacturers occasionally use their own extensions and sub-letters. Treat this page as a reading aid, not a specification — verify function assignments against the current edition of ANSI/IEEE C37.2 and the specific relay's instruction manual before you rely on them.
Related
- Single-Line Diagram Symbols (IEC + ANSI Cheat Sheet)
- How to Read a Single-Line Diagram
- Single-Line vs Three-Line Diagram — What's the Difference?
Spot an error or want a device number added? Email [email protected] and we'll fix it.